Siemens Energy & Automation, Inc.
Bellefontaine, OH 43311 U.S.A.
Hazardous voltage.
Will cause death or serious
injury.
Turn off and lock out all power supplying
the circuit breaker prior to cover(s)
removal or while cover(s) are removed
and when installing any internal or
external accessory.
Replace the cover(s) and shield(s)
before power supplying this device is
turned on.
Installing Sensitrip
TM
and SB Electronic Trip Units In Zone
Selective Interlocking or ACCESS
TM
Communications Systems
Mechanical Hazard.
Mechanism can cause
severe injury when cover is
removed.
Before removing cover
Remove motor fuse
Push open button
Push close button
Push open button again.
Page 1 of 7
Introduction
This Instruction Sheet provides the component selection, cabling and interconnect information to configure
Siemens Sensitrip MCCB and SB Systems Breaker ICCBs in either a Zone Selective Interlocking (ZSI)
network or in an ACCESS communications system. Installed ICCB SB breakers without communication
capability may be field upgraded by Siemens Field Service personnel only. MCCB breakers may be field
upgraded by Siemens Field Service or the end user. Refer to Figure 1 for a diagram of the possible intercon-
nect schemes described in the following scenarios.
Referenced Publications
The following publications are referenced in this instruction sheet, with the latest versions obtainable through the
local Siemens sales office:
_ ACCESS Systems Installation Guide [Manual SG-6028-01]
_ Isolated Multi-Drop RS-232 to RS-485 Converter, Operators Manual [Manual SG-6048-01]
_ Multiplexer Translator (MT), Information and Instruction Guide [Bulletin 2.21-1A]
_ Expansion Plug for Siemens Multiplexer Translator, Information and Instruction Sheet [Bulletin 2.21-2A]
_ Electronic Trip Unit for SB Encased Systems Breakers, Information and Instruction Guide [Bulletin 2.20-3A]
_ Sentron Systems Breaker, Energy Communicating Trip Unit, Information and Instruction Guide [Bulletin IPIM-
2208]
Referenced Components
The following components are referenced in this instruction sheet, with the latest versions obtainable through the
local Siemens sales office:
Siemens MTZ (Multiplexer Translator, Zone Interlock) [Cat. No. MTZ]  a microprocessor-based device
required for configuring and controlling a Zone Selective Interlocking (ZSI) network of up to eight (8) Sensitrip
or SB circuit breakers; multiple MTs may be interconnected for a total of 31 MTs and 248 breakers.
Siemens MTA (Multiplexer Translator, ACCESS) [Cat. No. MTA]  a microprocessor-based device for config-
uring and controlling up to eight (8) Sensitrip MCCBs and/or SB Trip Units within an ACCESS Communica-
tions System; multiple MTs may be interconnected for a total of 31 MTs and 248 breakers. The MTA also
provides Zone Selective Interlocking capability. (Note: the SB-EC trip unit is direct ACCESS compatible but
requires an MTZ or MTA for ZSI capability)
Siemens type EP (Expansion Plug) - an isolation device to connect Sensitrip MCCBs and SB trip units to an
MTA or MTZ. One (1) per trip unit when required.
Vue de la page 0
1 2 3 4 5 6 7

Résumé du contenu

Page 1 - Communications Systems

Siemens Energy & Automation, Inc.Bellefontaine, OH 43311 U.S.A.Hazardous voltage.Will cause death or seriousinjury.Turn off and lock out all power

Page 2

Siemens Energy & Automation, Inc.Bellefontaine, OH 43311 U.S.A.Page 2 of 7Hazardous voltage.Will cause death or seriousinjury.Turn off and lock ou

Page 3

Siemens Energy & Automation, Inc.Bellefontaine, OH 43311 U.S.A.Page 3 of 7Hazardous voltage.Will cause death or seriousinjury.Turn off and lock ou

Page 4

Siemens Energy & Automation, Inc.Bellefontaine, OH 43311 U.S.A.Page 4 of 7Hazardous voltage.Will cause death or seriousinjury.Turn off and lock ou

Page 5

Siemens Energy & Automation, Inc.Bellefontaine, OH 43311 U.S.A.Page 5 of 7Hazardous voltage.Will cause death or seriousinjury.Turn off and lock ou

Page 6

Siemens Energy & Automation, Inc.Bellefontaine, OH 43311 U.S.A.Installing SensitripTM and SB Electronic Trip Units In ZoneSelective Interlocking o

Page 7

Siemens Energy & Automation, Inc.Bellefontaine, OH 43311 U.S.A.Hazardous voltage.Will cause death or seriousinjury.Turn off and lock out all power